Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 12, 2017, 07:57 AM
  • 18 0352_18 0228 _12052017_005810.mp4

Date
05/12/2017
W/O
630481
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00714
PipeID
P14186
Time
12:57 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4494
Sewer Name
18 WASHINGTON BOULEVARD TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
WO_635481_TV18060_MAY2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0352
Downstream MH
18 0228
Dir. of Survey
Downstream
Length Surveyed
149.3 ft.
Total Length
149.3 ft.
Structural Index
3
Structural Quick
3C21
Structural Rating
65
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
69
Pipe schematic from manhole 18 0352 to 18 0228
MH: 18 0352MH: 18 0228downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 18 03520 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH0 ft. MWL - Water Level, 30 %of cross sectional area24.9 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES30.4 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES35.1 ft. CM - Crack Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES50.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start52.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"143.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish149.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0228

Observation photos (4)

  • Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    24.9 ft. - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    30.4 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

    35.1 ft. - Crack Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    50.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
24.9CM
52.6TFC
50.5CM
100.9TFC
149.3AMH18 0228
143.4CM
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK
0AMH18 0352
30.4CL
0MGOCAPPED LATERAL 9 O'CLOCK @ MH
0MWL
35.1CM

Properties (4)

additional_info
SC345303
custom_field_two
3
customer
LACSD
datetime
2017-05-12T00:57:55-07:00