Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2017, 05:32 AM
Date
05/16/2017
W/O
618894
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00258
PipeID
P03200
Time
10:32 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4455
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_618894_TV02057_MAY2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0646
Downstream MH
02 0692
Dir. of Survey
Downstream
Length Surveyed
164.4 ft.
Total Length
164.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2E00
O&M Rating
64
Overall Index
2
Overall Quick
Overall Rating
70
Pipe schematic from manhole 02 0646 to 02 0692
MH: 02 0646MH: 02 0692downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 06462 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES17.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"17.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES77.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"126.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.4 ft. MGO - General Observation - ACTIVE CONNECTIONS AT MH 3 AND 9 O'CLOCK164.4 ft. AMH - Downstream Manhole, Survey Ends - 02 0692164.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    6.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    17.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
164.4MGOACTIVE CONNECTIONS AT MH 3 AND 9 O'CLOCK
17.1TFC
164.4AMH02 0692
77.8TFA
0MWM
6.2CM
2DAGS
0MWL
0AMH02 0646
17.1CM
126.4TFC
164.4DAGS

Properties (4)

additional_info
SC345231
custom_field_two
4
customer
LACSD
datetime