- Date
- 07/28/2017
- W/O
- 0636060
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00325
- PipeID
- P21168
- Time
- 3:08 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0606
- Sewer Name
- A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
- City
- EL MONTE
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 22
- Purpose
- Routine Assessment
- Project
- 20170728MDM_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 63 in.
- Upstream MH
- A 0340
- Downstream MH
- A 1045
- Dir. of Survey
- Downstream
- Length Surveyed
- 63.6 ft.
- Total Length
- 63.6 ft.
- Structural Index
- 2
- Structural Quick
- 2100
- Structural Rating
- 2
- O&M Index
- 5
- O&M Quick
- 5141
- O&M Rating
- 9
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 11
Pipe schematic from manhole A 0340 to A 1045 Observation photos (5)

0 ft. - Water Mark, 100 %of cross sectional area

0 ft. - Water Level, 70 %of cross sectional area

2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERIN CONCRETE

42 ft. - General Observation - ZOOM 20'

63.1 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BLISTERING CONCRETE