Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2017, 08:32 AM
  • 18 0356_18 0355 _10052017_013338.mp4

Date
05/10/2017
W/O
630481
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00714
PipeID
P14190
Time
1:32 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4492
Sewer Name
18 WASHINGTON BOULEVARD TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
09
Purpose
Routine Assessment
Project
WO_635481_TV18060_MAY2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0356
Downstream MH
18 0355
Dir. of Survey
Downstream
Length Surveyed
227.4 ft.
Total Length
227.4 ft.
Structural Index
3
Structural Quick
3D21
Structural Rating
73
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
77
Pipe schematic from manhole 18 0356 to 18 0355
MH: 18 0356MH: 18 0355downstream0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 03560 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - CAPPED LATERAL 3 O'CLOCK @ MH0 ft. MWL - Water Level, 35 %of cross sectional area21.3 ft. CC - Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES25.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES47.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.5 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES87 ft. CC - Crack Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES95.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES111.7 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES126.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start142.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"206 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish227.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK227.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0355

Observation photos (7)

  • Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    21.3 ft. - Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    25.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

    72.5 ft. - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES

    87 ft. - Crack Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    96.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    111.7 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    126.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
227.3CM
0MWM
95.3TFC
0AMH18 0356
72.5CM
126.2CM
0MGOCONNECTION AT MH 9 O'CLOCK
21.3CC
142.9TFC
206TFC
227.4AMH18 0355
0MGOCAPPED LATERAL 3 O'CLOCK @ MH
227.3MGOCONNECTION AT MH 9 O'CLOCK
87CC
96.8CM
25.7CL
0MWL
47.1TFC
111.7CM

Properties (5)

additional_info
SC345301
custom_field_two
3
customer
LACSD
datetime
2017-05-10T01:32:37-07:00
sewer_category
Gravity