- Date
- 05/10/2017
- W/O
- 630481
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00714
- PipeID
- P14198
- Time
- 2:51 AM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K4492
- Sewer Name
- 18 WASHINGTON BOULEVARD TRUNK
- City
- WHITTIER
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 09
- Purpose
- Routine Assessment
- Project
- WO_635481_TV18060_MAY2017
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 18 in.
- Upstream MH
- 18 0364
- Downstream MH
- 18 0363
- Dir. of Survey
- Downstream
- Length Surveyed
- 108.7 ft.
- Total Length
- 108.7 ft.
- Structural Index
- 2
- Structural Quick
- 3223
- Structural Rating
- 12
- O&M Index
- 2
- O&M Quick
- 412C
- O&M Rating
- 46
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 58
Pipe schematic from manhole 18 0364 to 18 0363 Observation photos (6)

3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 05 o'clock, , within 8 inches of joint: YES, Start

11.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

19.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

34 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

49 ft. - Crack Multiple, from 12 to 02 o'clock, within 8 inches of joint: YES

83.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES