- Date
- 05/03/2017
- W/O
- 635407
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00077
- PipeID
- P08707
- Time
- 2:49 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K4442
- Sewer Name
- B JOINT OUTFALL B - UNIT 1E
- City
- ROSEMEAD
- Loc. details
- Main Highway - Suburban/Rural
- Location Code
- B
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 11
- Purpose
- Routine Assessment
- Project
- WO_635407_TV02153_MAY2017
- Material
- NRCP
- Shape
- Circular
- Height
- 18 in.
- Width
- 18 in.
- Upstream MH
- B 0239
- Downstream MH
- B 0238
- Dir. of Survey
- Downstream
- Length Surveyed
- 329.6 ft.
- Total Length
- 329.6 ft.
- Structural Index
- 3
- Structural Quick
- 3L2L
- Structural Rating
- 325
- O&M Index
- 2
- O&M Quick
- 2L00
- O&M Rating
- 130
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 455
Pipe schematic from manhole B 0239 to B 0238 Observation photos (6)

2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

99.7 ft. - Material Change, Vitrified clay pipe

102.6 ft. - Material Change, Concrete pipe (non-reinfored)

177.1 ft. - Material Change, Concrete pipe (non-reinfored)