Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2017, 08:05 AM
Date
05/18/2017
W/O
618894
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00258
PipeID
P03191
Time
1:05 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4556
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_618894_TV02057_MAY2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0638
Downstream MH
02 0639
Dir. of Survey
Upstream
Length Surveyed
163.5 ft.
Total Length
163.5 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
48
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
48
Pipe schematic from manhole 02 0638 to 02 0639
MH: 02 0638MH: 02 0639upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 06390 ft. MGO - General Observation - COCKROACHES IN MANHOLE0.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish66 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start82.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"114.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"130.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"150.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"163.5 ft. MWL - Water Level, 40 %of cross sectional area163.5 ft. AMH - Downstream Manhole, Survey Begins - 02 0638163.5 ft. MWM - Water Mark, 40 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    82.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
163.1MGOACTIVE CONNECTION AT MH 9 O'CLOCK
33TFC
0MWL
12.9TFC
0AMH02 0638
97.5TFC
163.5AMH02 0639
80.9TFA
48.9TFA
0MWM
82.3CM
163.5MGOCOCKROACHES IN MANHOLE
160.5CM

Properties (5)

additional_info
SC345232
custom_field_two
3
customer
LACSD
datetime
2017-05-18T01:05:45-07:00
sewer_category