Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 17, 2017, 10:53 AM
Date
05/17/2017
W/O
618894
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00258
PipeID
P03204
Time
3:53 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4455
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_618894_TV02057_MAY2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0649
Downstream MH
02 0650
Dir. of Survey
Upstream
Length Surveyed
201 ft.
Total Length
201 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2G00
O&M Rating
80
Overall Index
2
Overall Quick
Overall Rating
82
Pipe schematic from manhole 02 0649 to 02 0650
MH: 02 0649MH: 02 0650upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 06501.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish7 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES51.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"59.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"111.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"132.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"187.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"199 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start201 ft. MWL - Water Level, 10 %of cross sectional area201 ft. MWM - Water Mark, 30 %of cross sectional area201 ft. AMH - Downstream Manhole, Survey Begins - 02 0649

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    194 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
201AMH02 0650
13.4TFC
68.7TFA
89.3TBA
194CL
2DAGS
0MWL
149.4TFA
0MWM
199.6DAGS
109.8TFC
141.1TFA
0AMH02 0649

Properties (5)

additional_info
SC345231
custom_field_two
4
customer
LACSD
datetime
2017-05-17T03:53:27-07:00
sewer_category