Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2016, 04:48 AM
Date
09/14/2016
W/O
588247
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00028
PipeID
P11272
Time
9:48 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3583
Sewer Name
E JOINT OUTFALL E - UNIT 2
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
WO_588247_TV01123_AUG2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
E 0045
Downstream MH
E 0044
Dir. of Survey
Downstream
Length Surveyed
417.2 ft.
Total Length
417.2 ft.
Structural Index
3
Structural Quick
513B
Structural Rating
50
O&M Index
3
O&M Quick
3O00
O&M Rating
243
Overall Index
3
Overall Quick
Overall Rating
293
Pipe schematic from manhole E 0045 to E 0044
MH: E 0045MH: E 0044downstream0 ft. AMH - Upstream Manhole, Survey Begins - E 00450 ft. MWL - Water Level, 15 %of cross sectional area0.1 ft. MWM - Water Mark, 25 %of cross sectional area3.9 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start4 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES5.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start75.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish111.7 ft. SAV - Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO411.3 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish417.2 ft. AMH - Downstream Manhole, Survey Ends - E 0044

Observation photos (5)

  • Deposits Settled Other,  15 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    3.9 ft. - Deposits Settled Other, 15 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

    4 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

    75.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

  • Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO

    111.7 ft. - Surface Aggregate Visible, at 12 o'clock, within 8 inches of joint: NO

Observations (10)

DistanceCodeObservation
5.1SAV
75.2SAV
4SRV
411.3DSZ
417.2AMHE 0044
0AMHE 0045
3.9DSZ
111.7SAV
0MWL
0.1MWM

Properties (5)

additional_info
SC306177
custom_field_two
3
customer
LACSD
datetime
2016-09-14T21:48:27-07:00
sewer_category
Gravity