Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2017, 10:06 AM
  • 01 0836_01 0835_09052017_030822.mp4

Date
05/09/2017
W/O
630371
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00228
PipeID
P01665
Time
3:06 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4447
Sewer Name
01 WRIGHT ROAD TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
21
Purpose
Routine Assessment
Project
WO_630371_TV01261_APR2017
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
01 0836
Downstream MH
01 0835
Dir. of Survey
Downstream
Length Surveyed
271.5 ft.
Total Length
271.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
2
Overall Quick
Overall Rating
108
Pipe schematic from manhole 01 0836 to 01 0835
MH: 01 0836MH: 01 0835downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - LINED WITH CIPP.0 ft. AMH - Upstream Manhole, Survey Begins - 01 08362 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start65.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"269.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish271.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0835271.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
65.2TFA
2DAGS
271.5AMH01 0835
0MWM
269.7DAGS
208.5TFA
0MWL
0MGOLINED WITH CIPP.
271.5MGOACTIVE CONNECTION AT MH 3 AND 9 O'CLOCK
0AMH01 0836

Properties (5)

additional_info
SC345220
custom_field_two
4
customer
LACSD
datetime
2017-05-09T03:06:59-07:00
sewer_category
Gravity