Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2017, 07:40 AM
  • 29 0272_29 0261 _17032017_004047.mpg

Date
03/17/2017
W/O
624460
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00550
PipeID
P24179
Time
12:40 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4383
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
WO_624460_TV29035_MAR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0261
Downstream MH
29 0272
Dir. of Survey
Upstream
Length Surveyed
302.7 ft.
Total Length
302.7 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 29 0261 to 29 0272
MH: 29 0261MH: 29 0272upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 02726.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"22.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES42.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"51.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"59 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES59.8 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"81.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.7 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"170.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"196.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES212.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"225.3 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"231.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"260.8 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"302.7 ft. MWM - Water Mark, 5 %of cross sectional area302.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK302.7 ft. MWL - Water Level, 5 %of cross sectional area302.7 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK302.7 ft. AMH - Downstream Manhole, Survey Begins - 29 0261

Observation photos (6)

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

    41.9 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    77.4 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    106.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

    242.9 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    243.7 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    279.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
242.9TB
296.3TFC
132.2TFC
0MWM
106.3CL
156TF
191.9TFC
0MGOCONNECTION AT MH 9 O'CLOCK
41.9TB
0MWL
221.4TF
0MGOCONNECTION AT MH 6 O'CLOCK
89.9TF
0AMH29 0261
243.7CM
77.4TB
251.3TF
302.7AMH29 0272
279.8CM
71.5TFC
260.2TF

Properties (4)

additional_info
SC306892
custom_field_two
4
customer
LACSD
datetime
2017-03-17T00:40:08-07:00