Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2017, 07:00 AM
  • 29 0263_29 0262 _17032017_000109.mpg

Date
03/17/2017
W/O
624460
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00550
PipeID
P24167
Time
12:00 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4383
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
WO_624460_TV29035_MAR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0263
Downstream MH
29 0262
Dir. of Survey
Downstream
Length Surveyed
156.8 ft.
Total Length
156.8 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 29 0263 to 29 0262
MH: 29 0263MH: 29 0262downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 29 02630 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area27.2 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES95.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 6"148.5 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"152 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES156.8 ft. AMH - Downstream Manhole, Survey Ends - 29 0262

Observation photos (3)

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    27.2 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

    148.5 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    152 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
156.8AMH29 0262
0MGOCONNECTION AT MH 3 O'CLOCK
27.2CM
95.9TF
0MGOCONNECTION AT MH 6 O'CLOCK
148.5TB
152CL
0AMH29 0263
0MWL
0MWM

Properties (4)

additional_info
SC306892
custom_field_two
4
customer
LACSD
datetime
2017-03-17T00:00:04-07:00