Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2017, 05:18 AM
  • 29 0689_29 0264 _16032017_221900.mpg

Date
03/16/2017
W/O
624460
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00550
PipeID
P24169
Time
10:18 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4383
Sewer Name
29 WEST HILL STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
WO_624460_TV29035_MAR2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0689
Downstream MH
29 0264
Dir. of Survey
Downstream
Length Surveyed
348.5 ft.
Total Length
348.6 ft.
Structural Index
2
Structural Quick
4121
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 29 0689 to 29 0264
MH: 29 0689MH: 29 0264downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 06890 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area30.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"99.5 ft. JOM - Joint Offset Medium103.2 ft. JOM - Joint Offset Medium188.2 ft. CS - Crack Spiral, from 04 to 06 o'clock, within 8 inches of joint: YES192.9 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES194.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"197.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"258.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"301 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"339.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"348.6 ft. AMH - Downstream Manhole, Survey Ends - 29 0264

Observation photos (4)

  • Joint Offset Medium

    99.5 ft. - Joint Offset Medium

  • Joint Offset Medium

    103.2 ft. - Joint Offset Medium

  • Crack Spiral, from 04 to 06 o'clock, within 8 inches of joint: YES

    188.2 ft. - Crack Spiral, from 04 to 06 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    192.9 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
0AMH29 0689
0MWL
197.1TFC
103.2JOM
258.2TFC
99.5JOM
194.5TF
0MWM
339.7TF
74.9TF
30.1TFC
188.2CS
301TFC
348.6AMH29 0264
192.9FM

Properties (4)

additional_info
SC306892
custom_field_two
3
customer
LACSD
datetime
2017-03-16T22:18:29-07:00