Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2017, 09:59 AM
  • 15 0612_15 0611_042717_025954.mp4

Date
04/27/2017
W/O
630380
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00601
PipeID
P12547
Time
2:59 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4478
Sewer Name
15 DOUBLE AVENUE TRUNK
City
ARCADIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_630380_TV15205_APR2017
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0612
Downstream MH
15 0611
Dir. of Survey
Downstream
Length Surveyed
136.8 ft.
Total Length
136.8 ft.
Structural Index
3
Structural Quick
3H21
Structural Rating
143
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
143
Pipe schematic from manhole 15 0612 to 15 0611
MH: 15 0612MH: 15 0611downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 06120 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - ABANDONED MH2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7 ft. CM - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES21.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"23.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"25.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES30.9 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES40.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start80.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish136.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish136.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0611136.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

    7 ft. - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    25.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    30.9 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    40.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
136.8AMH15 0611
0AMH15 0612
2.5SAV
0MWL
80.3TF
136.7SAV
0MWM
30.9CM
40.4CM
23.7TF
25.3CL
0MGOABANDONED MH
129.8CM
7CM
21.5TF
136.8MGOCONNECTION AT MH 3 O'CLOCK
95.5TFC

Properties (5)

additional_info
SC345188
custom_field_two
3
customer
LACSD
datetime
2017-04-27T02:59:19-07:00
sewer_category