Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 21, 2017, 08:06 AM
  • 01 0433_01 0432_21032017_010731.mpg

Date
03/21/2017
W/O
624631
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00208
PipeID
P00915
Time
1:06 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4389
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_624631_TV01248_MAR2017
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0433
Downstream MH
01 0432
Dir. of Survey
Downstream
Length Surveyed
350.9 ft.
Total Length
350.9 ft.
Structural Index
3
Structural Quick
3M2E
Structural Rating
265
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
267
Pipe schematic from manhole 01 0433 to 01 0432
MH: 01 0433MH: 01 0432downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 04330 ft. MWM - Water Mark, 20 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start72.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"78 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"92 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"121.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"169.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"203 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start203 ft. RFB - Roots Fine Barrell, at 12 o'clock221.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"227 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"273.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"348.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish350.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0432350.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK CAPPED350.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    203 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Barrell, at 12 o'clock

    203 ft. - Roots Fine Barrell, at 12 o'clock

Observations (22)

DistanceCodeObservation
350.9AMH01 0432
350.9MGOCONNECTION AT MH 9 O'CLOCK CAPPED
350.9MGOCONNECTION AT MH 3 O'CLOCK
92TB
227TFC
125.5TF
78TFC
169.9TFC
121.1TF
277.1TFC
203CL
273.2TFC
221.7TFC
173.4TFC
0MWL
348.6SAV
203RFB
72.5TFC
2.1SAV
348.6CL
0AMH01 0433
0MWM

Properties (5)

additional_info
SC306898
custom_field_two
3
customer
LACSD
datetime
2017-03-21T01:06:19-07:00
sewer_category
Gravity