Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 20, 2017, 10:25 AM
  • 01 1383_01 1382_20042017_032517.mp4

Date
04/20/2017
W/O
630043
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00197
PipeID
P22188
Time
3:25 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4435
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
LYNWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
14
Purpose
Routine Assessment
Project
WO_630043_TV01008_APR2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 1382
Downstream MH
01 1383
Dir. of Survey
Upstream
Length Surveyed
283.4 ft.
Total Length
283.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2J00
O&M Rating
112
Overall Index
2
Overall Quick
Overall Rating
112
Pipe schematic from manhole 01 1382 to 01 1383
MH: 01 1382MH: 01 1383upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 13830.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish76.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"193.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.3 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"281.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start283.4 ft. AMH - Downstream Manhole, Survey Begins - 01 1382283.4 ft. MWM - Water Mark, 25 %of cross sectional area283.4 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0AMH01 1382
207.3TFC
283.3MGOACTIVE CONNECTION AT MH 3 O'CLOCK
89.7TFC
0MWM
2DAGS
0MWL
281DAGS
88.1TBA
283.4AMH01 1383

Properties (6)

additional_info
SC345207
custom_field_two
4
customer
LACSD
datetime
2017-04-20T03:25:00-07:00
sewer_category
Gravity
year_laid
35934