Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 5, 2017, 08:37 AM
  • Section#2_F 0159_F 0158__752017__G6775.mp4

Date
07/05/2017
W/O
0649649
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00043
PipeID
P10293
Time
1:37 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6775
Sewer Name
F JOINT OUTFALL F - UNIT 7A
City
CERRITOS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
20170705MDM_JOINT_OUTFALL_F_UNIT_7A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
51 in.
Upstream MH
F 0159
Downstream MH
F 0158
Dir. of Survey
Downstream
Length Surveyed
452.7 ft.
Total Length
452.7 ft.
Structural Index
4
Structural Quick
534Q
Structural Rating
383
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
383
Pipe schematic from manhole F 0159 to F 0158
MH: F 0159MH: F 0158downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:55AM0 ft. MGO - General Observation - MH CONN 3:00 ACTIVE0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR2 ft. MGO - General Observation - MAG COAT 40% 8:00 TO 4:00 START11.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR125.7 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG254.9 ft. SRV - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR373.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG452.2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG452.2 ft. MGO - General Observation - MAG COAT 40% FINISH452.7 ft. AMH - Downstream Manhole, Survey Ends - 3:30AM

Observation photos (6)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • General Observation - MAG COAT 40% 8:00 TO 4:00 START

    2 ft. - General Observation - MAG COAT 40% 8:00 TO 4:00 START

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    125.7 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    254.9 ft. - Surface Reinforcement Visible, from 09 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

    373.3 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG

Observations (14)

DistanceCodeObservation
0MWL
452.7AMH3:30AM
373.3SAMSEVERE AGG
452.2SAMSEVERE AGG
0AMH2:55AM
452.2MGOMAG COAT 40% FINISH
2SAMSEVERE AGG
2SRVCIRCUM REBAR
125.7SAMSEVERE AGG
0MGOMH CONN 3:00 ACTIVE
11.2SRVCIRCUM REBAR
0MWM
254.9SRVCIRCUM REBAR
2MGOMAG COAT 40% 8:00 TO 4:00 START

Properties (4)

custom_field_three
CIRCUM REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime
2017-07-05T01:37:37-07:00