Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 7, 2017, 08:45 AM
  • 16 0274_16 0273_772017_015834.mp4

Date
07/07/2017
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00652
PipeID
P13316
Time
1:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0583R
Sewer Name
16 CHAPEL AVENUE TRUNK, SECTION 1
City
SOUTH PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Maintenance Related
Project
20170717MDM_CHAPEL_AVENUE_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
16 0274
Downstream MH
16 0273
Dir. of Survey
Downstream
Length Surveyed
249 ft.
Total Length
249 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3321
O&M Rating
16
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole 16 0274 to 16 0273
MH: 16 0274MH: 16 0273downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:50AM5.5 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 4%14.4 ft. RFJ - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YESR - 2%23.5 ft. RFJ - Roots Fine Joint, from 02 to 03 o'clock, within 8 inches of joint: YESR - 1%31.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped45.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped48.3 ft. RFJ - Roots Fine Joint, from 02 to 04 o'clock, within 8 inches of joint: YESR - 2%57.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped69.2 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-95% ROOTS70.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start - 5% OR LESS81 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped96.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped98.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open106 ft. RMJ - Roots Medium Joint, from 08 to 04 o'clock, 10 %, within 8 inches of joint: YESR119.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped140.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped146.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open150.5 ft. RMJ - Roots Medium Joint, from 02 to 05 o'clock, 10 %, within 8 inches of joint: YESR151.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open157.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped169.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open175.4 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Finish - 5% OR LESS180.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped193.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped207.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped219.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped223.7 ft. RMJ - Roots Medium Joint, from 02 to 04 o'clock, 5 %, within 8 inches of joint: YESR232.5 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open249 ft. AMH - Downstream Manhole, Survey Ends - 2:20AM

Observation photos (1)

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start - 5% OR LESS

    70.9 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR, Start - 5% OR LESS

Observations (32)

DistanceCodeObservation
0MWL
48.3RFJ2%
223.7RMJ
150.5RMJ
151.4TBOpen
175.4RFJ5% OR LESS
193.1TFCCapped
14.4RFJ2%
146.9TFOpen
106RMJ
57.4TFCCapped
169.6TFOpen
249AMH2:20AM
140.4TFCCapped
207.4TFCCapped
0MGOConn. @ Mh, 9 O' Clock. Active
98.6TFOpen
180.8TFCCapped
96.2TFCCapped
45.6TFCCapped
232.5TFCOpen
219.7TFCCapped
157.5TFCCapped
69.2TFDOpen-95% ROOTS
0MWM
0AMH1:50AM
70.9RFJ5% OR LESS
119.6TFCCapped
31.2TFCCapped
81TFCCapped
5.5RFJ4%
23.5RFJ1%

Properties (2)

customer
LACSD
datetime