Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 19, 2017, 10:34 AM
  • 02 2259_02 0182_7192017_034001.mp4

Date
07/19/2017
W/O
0647471
Weather
Dry
Operator/Surveyor
Reveles
Sewer ID
Z00251
PipeID
P04539
Time
3:34 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0595
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Capital Improvement Program Assesment
Project
20170714VMR_DOWNEY_BELLFOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 2259
Downstream MH
02 0182
Dir. of Survey
Downstream
Length Surveyed
118.1 ft.
Total Length
118.1 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 2259 to 02 0182
MH: 02 2259MH: 02 0182downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03:45 am0 ft. MWM - Water Mark, 30 %of cross sectional area8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES10.1 ft. CC - Crack Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES21.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 4"24 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4"64.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4"67 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"112.7 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 4"118.1 ft. AMH - Downstream Manhole, Survey Ends - 04:05 am

Observations (11)

DistanceCodeObservation
118.1AMH04:05 am
24TF
21.2TFC
10.1CC
0MWL
0AMH03:45 am
112.7TF
0MWM
64.1TF
8CL
67TFC

Properties (3)

custom_field_two
4
customer
LACSD
datetime
2017-07-19T03:34:50-07:00