Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 5, 2017, 11:56 AM
  • 15 0667_15 0666 _05062017_061614.mp4

Date
06/05/2017
W/O
640776
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00602
PipeID
P12559
Time
4:56 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4539
Sewer Name
15 EL MONTE AVENUE TRUNK
City
EL MONTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
WO_640776_TV15208_JUN2017
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0667
Downstream MH
15 0666
Dir. of Survey
Downstream
Length Surveyed
295.4 ft.
Total Length
295.4 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
290
O&M Index
2
O&M Quick
2K11
O&M Rating
117
Overall Index
2
Overall Quick
Overall Rating
407
Pipe schematic from manhole 15 0667 to 15 0666
MH: 15 0667MH: 15 0666downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 06670 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start90.9 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: YES, 4"124.1 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 4"181.3 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"193.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"295.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0666295.4 ft. MGO - General Observation - CONNECTION AT 9 OC295.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish295.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish295.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish295.4 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - IN MH295.4 ft. MGO - General Observation - CONNECITON AT 3 OC

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
3SAV
295.4AMH15 0666
0AMH15 0667
295.4MGOCONNECTION AT 9 OC
124.1TB
193.2TFC
3SSS
295.4SSS
90.9TFC
0MWL
0MWM
295.4SAV
3DAGS
295.4DAGS
295.4VCIN MH
295.4MGOCONNECITON AT 3 OC
181.3TF

Properties (5)

additional_info
SC345354
custom_field_two
3
customer
LACSD
datetime
2017-06-05T04:56:50-07:00
sewer_category
Gravity