Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 31, 2017, 08:35 AM
  • 14 0564A_14 0564 _31052017_013614.mp4

Date
05/31/2017
W/O
635594
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00581
PipeID
P18660
Time
1:35 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4565
Sewer Name
14 TRUNK "E"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
17
Purpose
Routine Assessment
Project
WO_635594_TV14049_MAY2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0564
Downstream MH
14 0564A
Dir. of Survey
Upstream
Length Surveyed
212.3 ft.
Total Length
212.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2H00
O&M Rating
86
Overall Index
2
Overall Quick
Overall Rating
86
Pipe schematic from manhole 14 0564 to 14 0564A
MH: 14 0564MH: 14 0564Aupstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 14 0564A1.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish57.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"73 ft. OBR - Obstacles Rocks, 10 %of cross sectional area, from 05 to 07 o'clock160 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start212.3 ft. MWM - Water Mark, 20 %of cross sectional area212.3 ft. AMH - Downstream Manhole, Survey Begins - 14 0564212.3 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Obstacles Rocks, 10 %of cross sectional area, from 05 to 07 o'clock

    139.3 ft. - Obstacles Rocks, 10 %of cross sectional area, from 05 to 07 o'clock

Observations (10)

DistanceCodeObservation
0MWM
0AMH14 0564
212.3MGOACTIVE CONNECTION AT MH 3 O'CLOCK
52.3TFC
212.3AMH14 0564A
155.1TFC
139.3OBR
211.1DAGS
0MWL
2DAGS

Properties (5)

additional_info
SC345241
custom_field_two
4
customer
LACSD
datetime
2017-05-31T01:35:48-07:00
sewer_category