Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 31, 2017, 06:48 AM
  • 14 0567_14 0566 _30052017_234839.mp4

Date
05/30/2017
W/O
635594
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00581
PipeID
P18662
Time
11:48 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4565
Sewer Name
14 TRUNK "E"
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
18
Purpose
Routine Assessment
Project
WO_635594_TV14049_MAY2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0567
Downstream MH
14 0566
Dir. of Survey
Downstream
Length Surveyed
254.4 ft.
Total Length
254.4 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2I00
O&M Rating
100
Overall Index
2
Overall Quick
Overall Rating
102
Pipe schematic from manhole 14 0567 to 14 0566
MH: 14 0567MH: 14 0566downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 05672 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start96.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"188.5 ft. CS - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES202.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"252 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish254.4 ft. AMH - Downstream Manhole, Survey Ends - 14 0566

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

    188.5 ft. - Crack Spiral, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
0MWL
202.2TFC
252DAGS
188.5CS
96.5TFC
254.4AMH14 0566
2DAGS
0MWM
0AMH14 0567

Properties (5)

additional_info
SC345241
custom_field_two
4
customer
LACSD
datetime
2017-05-30T23:48:20-07:00
sewer_category
Gravity