Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2017, 07:51 AM
  • 15 0730_15 0729 _08062017_022756.mp4

Date
06/08/2017
W/O
640598
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00616
PipeID
P12623
Time
12:51 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4544
Sewer Name
15 MONROVIA OUTFALL TRUNK
City
,MONROVIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
09
Purpose
Routine Assessment
Project
WO_640598_TV15132_JUN2017
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 0730
Downstream MH
15 0729
Dir. of Survey
Downstream
Length Surveyed
654.8 ft.
Total Length
654.8 ft.
Structural Index
3
Structural Quick
3Y00
Structural Rating
390
O&M Index
2
O&M Quick
2Y00
O&M Rating
260
Overall Index
3
Overall Quick
Overall Rating
650
Pipe schematic from manhole 15 0730 to 15 0729
MH: 15 0730MH: 15 0729downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 07302.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.5 ft. MGO - General Observation - MAG COATING2.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start267.9 ft. MGO - General Observation - PAUSED VIDEO450.7 ft. MGO - General Observation - DISTANCE OVERRIDE, MEASURED USING WHEEL WALK654.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish654.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0729654.8 ft. MGO - General Observation - CONNECTION AT 9 OC654.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
654.8DAGS
450.7MGODISTANCE OVERRIDE, MEASURED USING WHEEL WALK
654.8AMH15 0729
2.5DAGS
0MWM
267.9MGOPAUSED VIDEO
0MWL
0AMH15 0730
2.5MGOMAG COATING
2.5SAV
654.8MGOCONNECTION AT 9 OC
654.8SAV

Properties (5)

additional_info
SC345359
custom_field_two
3
customer
LACSD
datetime
2017-06-08T00:51:25-07:00
sewer_category