- Date
- 05/23/2017
- W/O
- 619148
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00593
- PipeID
- P12955
- Time
- 1:49 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K4560
- Sewer Name
- 15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
- City
- ARCADIA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 08
- Purpose
- Routine Assessment
- Project
- WO_619148_TV15202_MAY2017
- Material
- NRCP
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 15 0755
- Downstream MH
- 15 0754
- Dir. of Survey
- Downstream
- Length Surveyed
- 96.5 ft.
- Total Length
- 96.5 ft.
- Structural Index
- 3
- Structural Quick
- 3C26
- Structural Rating
- 69
- O&M Index
- 2
- O&M Quick
- 412C
- O&M Rating
- 42
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 111
Pipe schematic from manhole 15 0755 to 15 0754 Observation photos (3)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

64.4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start