Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 26, 2017, 08:33 AM
  • 15 0790_15 0789 _26052017_013411.mp4

Date
05/26/2017
W/O
619148
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00593
PipeID
P12991
Time
1:33 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4563
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Routine Assessment
Project
WO_619148_TV15202_MAY2017
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0790
Downstream MH
15 0789
Dir. of Survey
Downstream
Length Surveyed
99 ft.
Total Length
99 ft.
Structural Index
2
Structural Quick
322C
Structural Rating
44
O&M Index
2
O&M Quick
2C00
O&M Rating
38
Overall Index
2
Overall Quick
Overall Rating
82
Pipe schematic from manhole 15 0790 to 15 0789
MH: 15 0790MH: 15 0789downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 07900 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start13.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"94.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start99 ft. MGO - General Observation - COCKROACHES IN MANHOLE99 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish99 ft. AMH - Downstream Manhole, Survey Ends - 15 078999 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish99 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    94.6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
99MGOCOCKROACHES IN MANHOLE
0MWL
99SSS
0AMH15 0790
99AMH15 0789
6.4SSS
2DAGS
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MWM
99SAP
13.2TFC
99DAGS
94.6SAP

Properties (5)

additional_info
SC345239
custom_field_two
2
customer
LACSD
datetime
2017-05-26T01:33:24-07:00
sewer_category