Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 18, 2017, 05:44 AM
  • 02 0635_02 0634_17052017_224513.mp4

Date
05/17/2017
W/O
618894
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00258
PipeID
P03187
Time
10:44 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4556
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
WO_618894_TV02057_MAY2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0635
Downstream MH
02 0634
Dir. of Survey
Downstream
Length Surveyed
352.7 ft.
Total Length
352.7 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
102
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
242
Pipe schematic from manhole 02 0635 to 02 0634
MH: 02 0635MH: 02 0634downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 06350 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start11.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"48 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"51.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"112.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"120.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"160.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"179 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start180.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"196.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"240.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"248.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"312.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"321.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"351.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish351.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish352.7 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK352.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0634

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    179 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
2DAGS
196.3TFC
179CM
352.7MGOACTIVE CONNECTION AT MH 3 O'CLOCK
352.7AMH02 0634
180.6TFA
248.5TFA
351.3CM
48TFA
351.3DAGS
0AMH02 0635
321.1TFC
0MWM
0MWL
240.6TFC
11.9TFC
51.9TFC
112.4TFA
120.4TFC
312.4TFA
160.4TFC

Properties (5)

additional_info
SC345232
custom_field_two
3
customer
LACSD
datetime
2017-05-17T22:44:17-07:00
sewer_category
Gravity