Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 19, 2017, 07:13 AM
  • 18 1017_18 1016 _19042017_001407.mp4

Date
04/19/2017
W/O
630156
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00677
PipeID
P14871
Time
12:13 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4268
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 1
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
WO_630156_TV18008_APR2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
18 1017
Downstream MH
18 1016
Dir. of Survey
Downstream
Length Surveyed
187.3 ft.
Total Length
187.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 18 1017 to 18 1016
MH: 18 1017MH: 18 1016downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 10170 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK ACTIVE0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - LINER0 ft. MWL - Water Level, 15 %of cross sectional area2.5 ft. MGO - General Observation - MAGNESIUM COATING START2.5 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start9.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"52.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"83.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"132.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"150.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"187.1 ft. MGO - General Observation - MAGNESIUM COATING END187.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish187.3 ft. AMH - Downstream Manhole, Survey Ends - 18 1015

Observation photos (1)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
150.9TFA
0AMH18 1017
187.1MGOMAGNESIUM COATING END
132.8TFA
83.3TFA
187.1DAGS
0MGOLATERAL AT MH 3 OCLOCK ACTIVE
187.3AMH18 1015
2.5MGOMAGNESIUM COATING START
52.8TFA
0MWM
9.8TFA
0MGOLINER
2.5DAGS
0MWL

Properties (6)

additional_info
SC306848
custom_field_two
4
customer
LACSD
datetime
2017-04-19T00:13:18-07:00
sewer_category
Gravity
year_laid