Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 31, 2017, 08:00 AM
  • 14 0563A_14 0563 _31052017_011227.mp4

Date
05/31/2017
W/O
635594
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00581
PipeID
P18658
Time
1:00 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4565
Sewer Name
14 TRUNK "E"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
17
Purpose
Routine Assessment
Project
WO_635594_TV14049_MAY2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0563
Downstream MH
14 0563A
Dir. of Survey
Upstream
Length Surveyed
88 ft.
Total Length
88 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2C00
O&M Rating
36
Overall Index
2
Overall Quick
Overall Rating
36
Pipe schematic from manhole 14 0563 to 14 0563A
MH: 14 0563MH: 14 0563Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 0563A0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish4 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES80.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"86 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start88 ft. MWL - Water Level, 10 %of cross sectional area88 ft. AMH - Downstream Manhole, Survey Begins - 14 056388 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 05 o'clock,  , within 8 inches of joint: YES

    84 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
0MWL
2DAGS
0AMH14 0563
7.2TFC
0MWM
88AMH14 0563A
88MGOACTIVE CONNECTION AT MH 3 O'CLOCK
88DAGS
84DAGS

Properties (4)

additional_info
SC345241
custom_field_two
4
customer
LACSD
datetime
2017-05-31T01:00:48-07:00