Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2017, 06:41 AM
  • 14 0100A_14 0100 _29032017_234151.mpg

Date
03/29/2017
W/O
624327
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00577
PipeID
P18122
Time
11:41 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4404
Sewer Name
14 TRUNK "A"
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
18
Purpose
Routine Assessment
Project
WO_624327_TV14017_MAR2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0100A
Downstream MH
14 0100
Dir. of Survey
Downstream
Length Surveyed
146.5 ft.
Total Length
146.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 14 0100A to 14 0100
MH: 14 0100AMH: 14 0100downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 0100A0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area1.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: YES2 ft. MMC - Material Change, Vitrified clay pipe23 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"46 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"72.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"118.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"146.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0100

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, at 08 o'clock,  , within 8 inches of joint: YES

    1.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, at 08 o'clock, , within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
0AMH14 0100A
23TFC
0MWM
146.5AMH14 0100
118.4TFC
1.8DAGS
2MMC
0MGOCONNECTION AT MH 3 O'CLOCK
46TFC
95.7TFC
0MWL
72.7TFC

Properties (4)

additional_info
SC345163
custom_field_two
4
customer
LACSD
datetime
2017-03-29T23:41:36-07:00