Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2017, 10:43 AM
  • 05 1093_05 1092_10032017_024342.mp4

Date
03/10/2017
W/O
624624
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00488
PipeID
P06327
Time
2:43 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4377
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
WO_624624_TV05328_MAR2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
05 1093
Downstream MH
05 1092
Dir. of Survey
Downstream
Length Surveyed
323.6 ft.
Total Length
323.6 ft.
Structural Index
3
Structural Quick
3F11
Structural Rating
100
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
104
Pipe schematic from manhole 05 1093 to 05 1092
MH: 05 1093MH: 05 1092downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 10930 ft. MWL - Water Level, 15 %of cross sectional area3.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES5.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"16.2 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES93.1 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES99.2 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES103.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"105.2 ft. CC - Crack Circumferential, from 07 to 02 o'clock, within 8 inches of joint: YES144.8 ft. CM - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES154.2 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES181.9 ft. CM - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES184.7 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Start205.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES207.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"319.2 ft. CM - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Finish323.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1092

Observation photos (10)

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    3.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    16.2 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    93.1 ft. - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    99.2 ft. - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 07 to 02 o'clock, within 8 inches of joint: YES

    105.2 ft. - Crack Circumferential, from 07 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

    144.8 ft. - Crack Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    154.2 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

    181.9 ft. - Crack Multiple, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Start

    184.7 ft. - Crack Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    205.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
323.6AMH05 1092
105.2CC
103.4TF
99.2FL
184.7CM
5.5TFA
144.8CM
0MWM
93.1CM
154.2CM
16.2CM
207.5TF
181.9CM
205.4DAGS
3.7DAGS
0AMH05 1093
319.2CM
0MWL

Properties (5)

additional_info
SC306886
custom_field_two
3
customer
LACSD
datetime
2017-03-10T02:43:33-08:00
sewer_category