Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 6, 2016, 09:37 AM
  • 18 0072A_18 0072 _06102016_025021.mp4

Date
10/06/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13887
Time
2:37 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3731
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0072A
Downstream MH
18 0072
Dir. of Survey
Downstream
Length Surveyed
340.4 ft.
Total Length
340.4 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
198
O&M Index
2
O&M Quick
2L11
O&M Rating
135
Overall Index
2
Overall Quick
Overall Rating
333
Pipe schematic from manhole 18 0072A to 18 0072
MH: 18 0072AMH: 18 0072downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 0072A0 ft. MWM - Water Mark, 15 %of cross sectional area4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start101.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"122.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 3"122.9 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES208.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"246.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"335.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish335.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish339.8 ft. VC - Vermin Cockroach340.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0072

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, from 02 to 04 o'clock,  , within 8 inches of joint: YES

    122.9 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, from 02 to 04 o'clock, , within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
339.8VC
335.5SAV
246.2TBA
0MWL
122.7TBA
208.4TFA
0AMH18 0072A
101.3TFA
4.4SAV
0MWM
335.6DAGS
4DAGS
340.4AMH18 0072
122.9DAE

Properties (5)

additional_info
SC303718
custom_field_two
3
customer
LACSD
datetime
2016-10-06T02:37:00-07:00
sewer_category
Gravity