Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 10, 2016, 11:45 AM
  • 18 0095_18 0094 _10102016_050705.mp4

Date
10/10/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13915
Time
4:45 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3733
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Material
NRCP
Shape
Square
Height
15 in.
Width
15 in.
Upstream MH
18 0094
Downstream MH
18 0095
Dir. of Survey
Upstream
Length Surveyed
289.9 ft.
Total Length
289.9 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
171
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
175
Pipe schematic from manhole 18 0094 to 18 0095
MH: 18 0094MH: 18 0095upstream0 ft. AMH - Upstream Manhole, Survey Ends - 18 00953.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish3.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish7.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"135.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"199.5 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"287.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start287.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start289.9 ft. AMH - Downstream Manhole, Survey Begins - 18 0094289.9 ft. MWL - Water Level, 10 %of cross sectional area289.9 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (2)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
90.4TBA
286SAV
0AMH18 0094
0MWL
286.8DAGS
282.2TFC
2SAV
2DAGS
0MWM
154.1TFC
289.9AMH18 0095

Properties (5)

additional_info
SC303720
custom_field_two
3
customer
LACSD
datetime
2016-10-10T04:45:57-07:00
sewer_category
Gravity