Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 4, 2016, 10:30 AM
  • 18 0091_18 0090 _04102016_034739.mp4

Date
10/04/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13910
Time
3:30 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3729
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0091
Downstream MH
18 0090
Dir. of Survey
Downstream
Length Surveyed
354.6 ft.
Total Length
354.7 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
146
Pipe schematic from manhole 18 0091 to 18 0090
MH: 18 0091MH: 18 0090downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00910.1 ft. MWM - Water Mark, 30 %of cross sectional area1.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start49.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"56.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"84.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"254.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 4"351 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish351.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish354.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0090

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
84.5TB
354.7AMH18 0090
2SAV
49.9TFC
1.4DAGS
56.5TFC
0MWL
351SAV
351.1DAGS
254.7TFC
0.1MWM
0AMH18 0091

Properties (5)

additional_info
SC303716
custom_field_two
3
customer
LACSD
datetime
2016-10-04T03:30:31-07:00
sewer_category