Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 6, 2016, 09:18 AM
  • 18 0074_18 0073 _06102016_023001.mp4

Date
10/06/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13889
Time
2:18 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3731
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0074
Downstream MH
18 0073
Dir. of Survey
Downstream
Length Surveyed
310.9 ft.
Total Length
310.9 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
180
O&M Index
2
O&M Quick
2L11
O&M Rating
127
Overall Index
2
Overall Quick
Overall Rating
307
Pipe schematic from manhole 18 0074 to 18 0073
MH: 18 0074MH: 18 0073downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 18 00740 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start6.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start18.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"92.1 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"120.2 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 4", 1"130.6 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"218.9 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 4", 1"231.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"297.7 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"306.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish307.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish310.8 ft. MGO - General Observation - CONNECTION AT MH 3 ACTIVE310.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0073310.9 ft. VC - Vermin Cockroach, within 8 inches of joint: NO

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 4", 1"

    120.2 ft. - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 4", 1"

  • Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 4", 1"

    218.9 ft. - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: NO, 4", 1"

Observations (18)

DistanceCodeObservation
120.2TBI
297.7TBA
0MWL
218.9TBI
0MGOCONNECTION AT MH 9 ACTIVE
6.1SAV
18.3TBA
306.5SAV
130.6TBA
0AMH18 0074
92.1TBA
0MWM
231.6TBA
2DAGS
310.9AMH18 0073
307.8DAGS
310.9VC
310.8MGOCONNECTION AT MH 3 ACTIVE

Properties (5)

additional_info
SC303718
custom_field_two
3
customer
LACSD
datetime
2016-10-06T02:18:00-07:00
sewer_category
Gravity