Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2016, 06:53 AM
  • 18 0117_18 0116 _05102016_001148.mp4

Date
10/04/2016
W/O
597011
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00698
PipeID
P13937
Time
11:53 PM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3730
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
WO_597011_TV18083_OCT2016
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0117
Downstream MH
18 0116
Dir. of Survey
Downstream
Length Surveyed
356.6 ft.
Total Length
356.7 ft.
Structural Index
3
Structural Quick
3M26
Structural Rating
228
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
232
Pipe schematic from manhole 18 0117 to 18 0116
MH: 18 0117MH: 18 0116downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 01170 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start60.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"66.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"95.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES100.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO109.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"110.6 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES115.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"161.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"167.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"180.9 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES205.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES210.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"216.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"245.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES261.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"268 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"310.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"316.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"333.8 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES345.8 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES353 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish354.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish356.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0116

Observation photos (9)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    95.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO

    100.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    110.6 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    180.9 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    205.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    245.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    333.8 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    345.8 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
2SAV
109.6TF
95.4CL
216.2TFC
180.9CM
268TFC
333.8CL
210.2TFC
0AMH18 0117
261.9TFA
115.2TFC
110.6CM
245.3CL
100.2CL
0MWL
354.3DAGS
60.3TF
356.7AMH18 0116
353SAV
0MWM
345.8CL
161.4TF
66.4TFC
310.8TFC
316.7TFC
2.1DAGS
205.5CL
167.1TFC

Properties (5)

additional_info
SC303717
custom_field_two
3
customer
LACSD
datetime
2016-10-04T23:53:00-07:00
sewer_category