Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 27, 2016, 06:36 AM
  • H 1229_H 1228 _09262016_233729.mp4

Date
09/26/2016
W/O
596964
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01182
PipeID
P17653
Time
11:36 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3768
Sewer Name
H JOINT OUTFALL H - UNIT 8K RELIEF
City
AZUSA
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
WO_596964_TV15041_OCT2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
H 1229
Downstream MH
H 1228
Dir. of Survey
Downstream
Length Surveyed
432.7 ft.
Total Length
432.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole H 1229 to H 1228
MH: H 1229MH: H 1228downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 12290 ft. MWL - Water Level, 25 %of cross sectional area0.1 ft. MWM - Water Mark, 40 %of cross sectional area0.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start0.4 ft. MGO - General Observation - MAG COATING 75%182 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start344.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"389.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"430.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish430.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish432.7 ft. AMH - Downstream Manhole, Survey Ends - H 1228

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    0.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    182 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0.4MGOMAG COATING 75%
344.2TFA
0.1MWM
430.8DAGS
182SAP
0AMHH 1229
389.6TFA
432.7AMHH 1228
0.1DAGS
0MWL
430.8SAP

Properties (6)

additional_info
SC306303
custom_field_two
3
customer
LACSD
datetime
2016-09-26T23:36:49-07:00
sewer_category
Gravity
year_laid
30904