Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 1, 2017, 10:35 AM
  • 01 1126_01 1125_01032017_023604.mp4

Date
03/01/2017
W/O
619125
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00210
PipeID
P01978
Time
2:35 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
4362
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
WO_619125_TV01246_FEB2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1126
Downstream MH
01 1125
Dir. of Survey
Downstream
Length Surveyed
280 ft.
Total Length
280 ft.
Structural Index
3
Structural Quick
3J21
Structural Rating
164
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
167
Pipe schematic from manhole 01 1126 to 01 1125
MH: 01 1126MH: 01 1125downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11264.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES6.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start21.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"62.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"67.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"113.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"143.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"218.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"246.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"278.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish280 ft. AMH - Downstream Manhole, Survey Ends - 01 1125

Observation photos (3)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    4.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    143.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (19)

DistanceCodeObservation
246.8TF
195.7TF
149.5TF
21.3TF
218.8TF
278.5CM
0MWM
62.2TFA
0MWL
106.1TF
6.9CM
4.4CL
0AMH01 1126
67.4TF
113.7TF
143.6TB
175.3TF
241.6TF
280AMH01 1125

Properties (5)

additional_info
SC306874
custom_field_two
3
customer
LACSD
datetime
2017-03-01T02:35:08-08:00
sewer_category
Gravity