Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 14, 2017, 10:19 AM
  • 29 0255_29 0254 _02142017_022024.mp4

Date
02/14/2017
W/O
619119
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00544
PipeID
P24158
Time
2:19 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4241
Sewer Name
29 WEST HILL STREET TRUNK
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
WO_619119_TV29089_FEB2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
29 0254
Downstream MH
29 0255
Dir. of Survey
Upstream
Length Surveyed
160.8 ft.
Total Length
160.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2E00
O&M Rating
62
Overall Index
2
Overall Quick
Overall Rating
62
Pipe schematic from manhole 29 0254 to 29 0255
MH: 29 0254MH: 29 0255upstream0 ft. AMH - Upstream Manhole, Survey Ends - 29 02551.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE1.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish87.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"123.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"147.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start160.8 ft. AMH - Downstream Manhole, Survey Begins - 29 0254160.8 ft. MWM - Water Mark, 15 %of cross sectional area160.8 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
160.8AMH29 0255
67.5TFC
0AMH29 0254
2DAGS
0MWM
0MWL
159.3MGOCOCKROACHES IN MANHOLE
37.4TFC
73.2TFC
159.3DAGS
13.3TFC

Properties (5)

additional_info
SC306744
custom_field_two
4
customer
LACSD
datetime
2017-02-14T02:19:55-08:00
sewer_category
Gravity