Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 11, 2016, 08:26 AM
  • 08 0476_08 0475 _20161011_021742.mpg

Date
10/11/2016
W/O
596976
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00025
PipeID
P00533
Time
1:26 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3735
Sewer Name
08 216TH STREET RELOCATION TRUNK
City
CARSON, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
WO_596976_TV08101_OCT2016
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
08 0476
Downstream MH
08 0475
Dir. of Survey
Downstream
Length Surveyed
714.3 ft.
Total Length
714.3 ft.
Structural Index
5
Structural Quick
5100
Structural Rating
5
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 08 0476 to 08 0475
MH: 08 0476MH: 08 0475downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 04762 ft. MGO - General Observation - MAG HYDROXIDE COATING STAR8.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start8.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start713.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish713.2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish714.3 ft. MSA - Survey Abandoned - BOAT HUNG UP ON DEBRIS IN PIPE

Observation photos (3)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    8.9 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.9 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    713.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (9)

DistanceCodeObservation
8.9DAGS
0MWL
2MGOMAG HYDROXIDE COATING STAR
0MWM
8.9SRV
713.2SRV
714.3MSABOAT HUNG UP ON DEBRIS IN PIPE
713.2DAGS
0AMH08 0476

Properties (5)

additional_info
SC303722
custom_field_two
5
customer
LACSD
datetime
2016-10-11T01:26:44-07:00
sewer_category
Gravity