Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 9, 2016, 11:00 AM
  • F 0252_F 0251 _11222016_110912.mp4

Date
11/09/2016
W/O
596944
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00035
PipeID
P10174
Time
3:00 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3877
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
CERRITOS
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
WO_596944_TV02313_OCT2016
Material
RGRCP
Shape
Circular
Height
81 in.
Width
81 in.
Upstream MH
F 0252
Downstream MH
F 0251
Dir. of Survey
Downstream
Length Surveyed
145.2 ft.
Total Length
145.2 ft.
Structural Index
5
Structural Quick
5100
Structural Rating
5
O&M Index
1
O&M Quick
2112
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole F 0252 to F 0251
MH: F 0252MH: F 0251downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK BULKHEAD0 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK BULKHEAD0 ft. AMH - Upstream Manhole, Survey Begins - F 02520 ft. MWM - Water Mark, 30 %of cross sectional area2.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - REBAR11.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start47.5 ft. LL - Alignment Left, 10 %133.9 ft. VC - Vermin Cockroach139.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish141 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish144.5 ft. MGO - General Observation - REBAR145.2 ft. AMH - Downstream Manhole, Survey Ends - F 0251

Observation photos (4)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - REBAR

    2.1 ft. - General Observation - REBAR

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    11.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - REBAR

    144.5 ft. - General Observation - REBAR

Observations (14)

DistanceCodeObservation
139.9DAGS
0MWL
0MGOLATERAL AT MH 9 OCLOCK BULKHEAD
144.5MGOREBAR
133.9VC
11.9DAGS
145.2AMHF 0251
2.1SRV
0MGOLATERAL AT MH 3 OCLOCK BULKHEAD
47.5LL
0AMHF 0252
141SRV
0MWM
2.1MGOREBAR

Properties (5)

additional_info
SC305207
custom_field_two
2
customer
LACSD
datetime
2016-11-09T03:00:23-08:00
sewer_category
Gravity