Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 22, 2017, 05:46 AM
  • 01 0419_01 0418A_21032017_231418.mpg

Date
03/21/2017
W/O
625686
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00208
PipeID
P00900
Time
10:46 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4393
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_625686_TV01030_MAR2017
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0419
Downstream MH
01 0418A
Dir. of Survey
Downstream
Length Surveyed
164.6 ft.
Total Length
164.7 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
96
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
96
Pipe schematic from manhole 01 0419 to 01 0418A
MH: 01 0419MH: 01 0418Adownstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 04190 ft. MWM - Water Mark, 15 %of cross sectional area2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start44.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"49.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"67.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"69.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"98.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"121.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"123.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"146.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish164.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0418A164.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
0MWL
67.3TFC
44.1TFC
123.7TFC
49.4TFC
164.7SAV
95.9TF
0AMH01 0419
98.3TFC
2.6SAV
0MWM
164.7AMH01 0418A
121.1TFC
164.7MGOCONNECTION AT MH 9 O'CLOCK
128.9TF
69.9TF
146.9TF

Properties (5)

additional_info
SC345153
custom_field_two
3
customer
LACSD
datetime
2017-03-21T22:46:07-07:00
sewer_category