Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2017, 12:37 AM
  • 01 0541_01 0540_031017_031248.mp4

Date
02/17/2017
W/O
624605
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00206
PipeID
P01029
Time
4:37 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
4319
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_624605_TV01232_MAR2017
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0541
Downstream MH
01 0540
Dir. of Survey
Downstream
Length Surveyed
318.2 ft.
Total Length
318.2 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
189
O&M Index
2
O&M Quick
2L00
O&M Rating
126
Overall Index
3
Overall Quick
Overall Rating
315
Pipe schematic from manhole 01 0541 to 01 0540
MH: 01 0541MH: 01 0540downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05413.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start29 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"69.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"72.1 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"119.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"165.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"188.7 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"249.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"269.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"300.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"312.4 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"318.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish318.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0540318.2 ft. MGO - General Observation - ABANDONED CONNECTION AT 9 O CLOCK318.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
269.9TF
318.2DAGS
165.9TF
312.4TF
29TFA
119.8TF
0MWL
318.2AMH01 0540
3.9SAV
300.1TF
0MWM
69.6TF
318.2MGOABANDONED CONNECTION AT 9 O CLOCK
249.8TF
188.7TF
318.2SAV
3.9DAGS
72.1TF
0AMH01 0541

Properties (5)

additional_info
SC318732
custom_field_two
3
customer
LACSD
datetime
2017-02-17T16:37:24-08:00
sewer_category
Gravity