Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2017, 12:39 AM
  • 01 0397_01 0396_031017_010115.mp4

Date
02/17/2017
W/O
624309
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00208
PipeID
P00876
Time
4:39 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
4318
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
WO_624309_TV01032_MAR2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0397
Downstream MH
01 0396
Dir. of Survey
Downstream
Length Surveyed
355.2 ft.
Total Length
355.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
140
Pipe schematic from manhole 01 0397 to 01 0396
MH: 01 0397MH: 01 0396downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 03970 ft. MWL - Water Level, 10 %of cross sectional area3.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start27.9 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"49.2 ft. MGO - General Observation - PIPE LINED73.4 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"165.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"206.2 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"257.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"355.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0396355.2 ft. MGO - General Observation - CONNECTION AT 3 O CLOCK355.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
27.9TF
355.2AMH01 0396
355.2MGOCONNECTION AT 3 O CLOCK
3.9DAGS
206.2TF
49.2MGOPIPE LINED
165.2TF
355.2DAGS
73.4TF
0MWM
257.6TF
0AMH01 0397
0MWL

Properties (6)

additional_info
SC318731
custom_field_two
4
customer
LACSD
datetime
2017-02-17T16:39:25-08:00
sewer_category
Gravity
year_laid
35628