Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2017, 09:49 AM
  • 17 0016_17 0015 _02082017_022439.mp4

Date
02/08/2017
W/O
618954
Weather
Light Rain
Operator/Surveyor
JUAN B
Sewer ID
Z00668
PipeID
P13740
Time
1:49 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4234
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
07
Purpose
Routine Assessment
Project
WO_618954_TV17003_FEB2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
17 0016
Downstream MH
17 0015
Dir. of Survey
Downstream
Length Surveyed
364.8 ft.
Total Length
364.8 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
216
O&M Index
2
O&M Quick
2M00
O&M Rating
144
Overall Index
3
Overall Quick
Overall Rating
360
Pipe schematic from manhole 17 0016 to 17 0015
MH: 17 0016MH: 17 0015downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 17 00160 ft. MWM - Water Mark, 20 %of cross sectional area3.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"42.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"54.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"61.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"93.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"129.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"148 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"187.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"194.1 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"364.8 ft. AMH - Downstream Manhole, Survey Ends - 17 0015364.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish364.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
11.6TF
148TF
61.4TF
0MWL
364.8AMH17 0015
0AMH17 0016
194.1TF
93.1TB
129.7TFC
187.4TFC
54.2TF
6.1CM
42.7TF
364.8CM
0MWM
364.8DAGS
3.5DAGS

Properties (5)

additional_info
SC306736
custom_field_two
4
customer
LACSD
datetime
2017-02-08T01:49:41-08:00
sewer_category
Gravity