- Date
- 02/06/2017
- W/O
- 618954
- Weather
- Light Rain
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00668
- PipeID
- P13738
- Time
- 3:52 AM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K4232
- Sewer Name
- 17 DISTRICT #17 MAIN TRUNK
- City
- ALTADENA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 17
- Page No.
- 07
- Purpose
- Routine Assessment
- Project
- WO_618954_TV17003_FEB2017
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Width
- 15 in.
- Upstream MH
- 17 0012
- Downstream MH
- 17 0013
- Dir. of Survey
- Upstream
- Length Surveyed
- 493.8 ft.
- Total Length
- 493.8 ft.
- Structural Index
- 0
- Structural Quick
- 0000
- Structural Rating
- 0
- O&M Index
- 2
- O&M Quick
- 322S
- O&M Rating
- 207
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 207
Pipe schematic from manhole 17 0012 to 17 0013 Observation photos (3)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

109.7 ft. - Roots Medium Lateral, from 12 to 04 o'clock, 20 %, within 8 inches of joint: YES

135.9 ft. - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YESR