Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 10, 2016, 11:06 AM
  • 02 1795_02 1794_10102016_040635.mp4

Date
10/10/2016
W/O
596913
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00292
PipeID
P04140
Time
4:06 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3426
Sewer Name
02 MONTEREY PARK RELIEF TRUNK
City
MONEREY PARK
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
WO_596913_TV02215_OCT2016
Material
NRCP
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
02 1795
Downstream MH
02 1794
Dir. of Survey
Downstream
Length Surveyed
330.4 ft.
Total Length
330.4 ft.
Structural Index
4
Structural Quick
4L3L
Structural Rating
451
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
451
Pipe schematic from manhole 02 1795 to 02 1794
MH: 02 1795MH: 02 1794downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 17951.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.6 ft. FM - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES10 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES16 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start72.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"74.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"113.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"116.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"122.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"158.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"182.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"204.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"230.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"251.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"272.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"294.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"311.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"327.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish327.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1794

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    1.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

    3.6 ft. - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    10 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
272.5TF
311.6TF
1.9SAV
230.5TF
0MWL
0MWM
113.9TF
10FM
327.7FM
0AMH02 1795
251.4TF
16FM
116.4TF
158.8TF
74.3TF
122.4TF
294.1TFA
204.3TF
182.8TF
327.7SAV
3.6FM
72.3TF
330.4AMH02 1794

Properties (5)

additional_info
SC303460
custom_field_two
2
customer
LACSD
datetime
2016-10-10T04:06:32-07:00
sewer_category
Gravity