Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2017, 11:07 AM
  • 15 1165_15 1164 _01072017_032036.mpg

Date
01/07/2017
W/O
616852
Weather
Light Rain
Operator/Surveyor
R.VARGAS
Sewer ID
Z00635
PipeID
P25911
Time
3:07 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4069
Sewer Name
15 TYLER AVENUE RELIEF TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
17
Purpose
Routine Assessment
Project
WO_616852_DISTRICT15_JAN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 1165
Downstream MH
15 1164
Dir. of Survey
Downstream
Length Surveyed
288 ft.
Total Length
288 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2J00
O&M Rating
114
Overall Index
2
Overall Quick
Overall Rating
114
Pipe schematic from manhole 15 1165 to 15 1164
MH: 15 1165MH: 15 1164downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 11652.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAGNESIUM H.O. START35.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"54.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"130.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"196.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"224.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"284.7 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH284.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish288 ft. AMH - Downstream Manhole, Survey Ends - 15 1164288 ft. MGO - General Observation - CCTV FOOTAGE DIFFERENT FROM SPREAD SHEET

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
54.1TFA
130.1TFA
284.7MGOMAGNEZIUM H.O. FINISH
284.7DAGS
288AMH15 1164
0MWM
35.9TFA
196.2TFA
0MWL
224.6TFA
0AMH15 1165
2.1DAGS
288MGOCCTV FOOTAGE DIFFERENT FROM SPREAD SHEET
2.1MGOMAGNESIUM H.O. START

Properties (6)

additional_info
SC318610
custom_field_two
4
customer
LACSD
datetime
2017-01-07T03:07:05-08:00
sewer_category
Gravity
year_laid
39519