Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2017, 10:52 AM
  • 15 1166_15 1165 _01072017_030555.mpg

Date
01/07/2017
W/O
616852
Weather
Light Rain
Operator/Surveyor
R.VARGAS
Sewer ID
Z00635
PipeID
P25912
Time
2:52 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4069
Sewer Name
15 TYLER AVENUE RELIEF TRUNK
City
EL MONTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
17
Purpose
Routine Assessment
Project
WO_616852_DISTRICT15_JAN2017
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 1166
Downstream MH
15 1165
Dir. of Survey
Downstream
Length Surveyed
312.5 ft.
Total Length
312.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
124
Pipe schematic from manhole 15 1166 to 15 1165
MH: 15 1166MH: 15 1165downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 11660 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE0 ft. MWM - Water Mark, 15 %of cross sectional area2.7 ft. MGO - General Observation - MAGNESIUM H.O. START2.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start41.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"109.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"181.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"260.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"310.6 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH310.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish312.6 ft. MGO - General Observation - CCTV FOOTAGE DIFFERENT FROM SPREAD SHEET312.6 ft. AMH - Downstream Manhole, Survey Ends - 15 1165

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
260.9TFA
41.4TFA
2.7MGOMAGNESIUM H.O. START
0MWL
310.6MGOMAGNEZIUM H.O. FINISH
310.6DAGS
312.6MGOCCTV FOOTAGE DIFFERENT FROM SPREAD SHEET
0AMH15 1166
0MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
181.7TFA
2.7DAGS
109.7TFA
0MWM
312.6AMH15 1165

Properties (6)

additional_info
SC318610
custom_field_two
4
customer
LACSD
datetime
2017-01-07T02:52:08-08:00
sewer_category
Gravity
year_laid
39519