Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 23, 2017, 11:18 AM
  • 22 0235_22 0234 _23012017_031825.mpg

Date
01/23/2017
W/O
613646
Weather
Light Rain
Operator/Surveyor
R.VARGAS
Sewer ID
Z00793
PipeID
P16517
Time
3:18 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4086
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
35
Purpose
Routine Assessment
Project
WO_613646_TV22160_JAN2017
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
22 0235
Downstream MH
22 0234
Dir. of Survey
Downstream
Length Surveyed
411.4 ft.
Total Length
411.4 ft.
Structural Index
3
Structural Quick
3O00
Structural Rating
243
O&M Index
2
O&M Quick
3N2O
O&M Rating
385
Overall Index
3
Overall Quick
Overall Rating
628
Pipe schematic from manhole 22 0235 to 22 0234
MH: 22 0235MH: 22 0234downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02350 ft. MWL - Water Level, 30 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAGNESIUM H.O. START5.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"9 ft. VC - Vermin Cockroach9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"20.4 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock, Start - DEBRIS NOT VISIBLE54.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"57.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"100 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"103.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"148.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"151.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"151.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"156.8 ft. MGP - General Photograph156.8 ft. OBZ - Obstacles Other, 20 %of cross sectional area, from 04 to 08 o'clock, Finish - DEBRIS NOT VISIBLE177.5 ft. OBZ - Obstacles Other, 15 %of cross sectional area, from 04 to 08 o'clock, Start - DEBRIS NOT VISIBLE197.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"200.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"248.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"252.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"297.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"300.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"346.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"350.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"394.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"398 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"407.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish407.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish407.8 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH411.4 ft. OBZ - Obstacles Other, 15 %of cross sectional area, from 04 to 08 o'clock, Finish - DEBRIS NOT VISIBLE411.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0234

Observation photos (3)

  • Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    156.8 ft. - General Photograph

Observations (35)

DistanceCodeObservation
151.3TFC
156.8MGP
9VC
394.8TFC
5.7TFA
57.9TFA
398TFC
2.1DAGS
9TFC
148.4TFC
0MWM
252.5TFC
156.8OBZDEBRIS NOT VISIBLE
100TFC
411.4OBZDEBRIS NOT VISIBLE
197.4TFC
346.3TFA
411.4AMH22 0234
151.2TBA
20.4OBZDEBRIS NOT VISIBLE
103.4TFC
248.7TFC
300.6TFC
200.3TFC
407.7DAGS
407.8MGOMAGNEZIUM H.O. FINISH
2.1SAV
54.9TFC
407.7SAV
177.5OBZDEBRIS NOT VISIBLE
297.2TFC
350.1TFC
0AMH22 0235
2.1MGOMAGNESIUM H.O. START
0MWL

Properties (5)

additional_info
SC318627
custom_field_two
3
customer
LACSD
datetime
2017-01-23T03:18:01-08:00
sewer_category
Gravity