Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 20, 2017, 09:42 AM
  • 22 0251_22 0250_20012017_011828.mpg

Date
01/20/2017
W/O
613646
Weather
Light Rain
Operator/Surveyor
R.VARGAS
Sewer ID
Z00793
PipeID
P16533
Time
1:42 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4085
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WETS COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
36
Purpose
Routine Assessment
Project
WO_613646_TV22160_JAN2017
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
22 0251
Downstream MH
22 0250
Dir. of Survey
Downstream
Length Surveyed
304.1 ft.
Total Length
304.1 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
184
O&M Index
2
O&M Quick
2K11
O&M Rating
121
Overall Index
3
Overall Quick
Overall Rating
305
Pipe schematic from manhole 22 0251 to 22 0250
MH: 22 0251MH: 22 0250downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK ACTIVE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 02512.1 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - MAGNESIUM H.O. START6 ft. VC - Vermin Cockroach, within 8 inches of joint: NO6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"14.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES48.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"94.9 ft. MGP - General Photograph100.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"103.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"148.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"197.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"243 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"249.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"300.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish300.9 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH300.9 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish304.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED304.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0250

Observation photos (4)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    14.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Photograph

    94.9 ft. - General Photograph

Observations (23)

DistanceCodeObservation
243TFA
304.1MGOCONNECTION AT MH 3 O'CLOCK CAPPED
103.1TFA
249.1TFA
48.7TFA
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK ACTIVE
14.1FM
300.9SAV
2.1DAGS
0MWL
2.1SAV
148.9TFA
94.9MGP
304.1AMH22 0250
197.7TFA
6VC
300.9MGOMAGNEZIUM H.O. FINISH
6TFC
2.1MGOMAGNESIUM H.O. START
300.9DAGS
100.4TFC
0AMH22 0251

Properties (5)

additional_info
SC318626
custom_field_two
3
customer
LACSD
datetime
2017-01-20T01:42:04-08:00
sewer_category
Gravity